pressure vacuum breaker

Backflow device configured with a spring loaded float and an independent spring loaded check valve. Check valve which is designed to close with the aid of a spring when flow stops. It also has an air inlet valve which is designed to open when the internal pressure is one psi above atmospheric pressure so that no non-potable liquid may be siphoned back into the potable water system. Being spring loaded it does not rely upon gravity as does the atmospheric vacuum breaker. This assembly includes resilient seated shut-off valves and test cocks. The PVB must be installed at least twelve (12) inches above all downstream piping and outlets. The PVB may be used to protect against a pollutant or contaminant, however, it may only be used to protect against backsiphonage. It is not acceptable protection against backpressure.

Authorization Path: 2.4.5.2.17.0